Basic Info.
Type
Linear Heat Detector
Product Description
MS2000 Analog Adjustable Linear Heat Detection System is a kind of four-core high-performance analog linear heat detector, with high adaptability and high performance-price ratio, which could be widely applied in places of industry, commerce and super heat dangerous area. Linear heat cable has high resistance and the insulating layers of its four core conductors are made of a kind of special NTC (negative temperature coefficient) material and its electrical control unit could reflect the fluctuation of system temperature by monitoring the fluctuation of material resistance.
MS2000 Linear Heat Detection(abbr LHD) System Consists: a. LHD Cable b. Control Unit
LHD Cable
1. Classification
Conventional Type This Type of LHD cable is the most widely used with strong stability.
CR/OD Type CR/OD Type not only has good UV resistance and good weather resistance, strongly recommended for outdoor using even under bad weather conditions, but also with high performance of acid resistant, alkali-resistant, salt spray resistant.
EP Type Explosion Proof Type, two main application environments: harsh EMI environment and explosive hazardous environment. The outer jacket of this type is protected by woven metal mesh with good performance of anti-EMI and eliminating the surface static of the LHD cable. We can us this type LHD cable in explosive hazardous environment with safety fence. During the installation, please make grounding connection of the woven metal mesh. Used in harsh EMI environment, single end grounding connection or double ends grounding connection should be specified after analysis of the interference sources
2. Structure & Installation
While wiring, the two red wires and two white wires are respectively connected to MS2000 linear detector interface and are strand-connected at the terminal, which is that red wire and white wire form a circuit for detector.
The system detects the resistance fluctuation of linear heat sensing cable resulted from the fluctuation of circuit temperature---i.e. when temperature rises, resistance drops. This fluctuation is monitored through linear detector interface of linear heat sensing cable. When it reaches preset alarm threshold value, output alarming signal. This feature allows the system to have the ability to detect fire in point or in line of whole circuit, which is that the system could detect the temperature fluctuation in certain point as well as certain area. After alarming, it could automatically restore to working condition.
Because the signal of linear heat sensing cable is analog signal, the application length shall not be overlong. Normally we regulate that the length for one tape is 200m. About the application issues, see detailed introduction in following part of the article.
3. Features and benefits
High adaptability: it could be applied in narrow, poor and dangerous environment conditions.
Good compatibility, MS2000 linear detector interface has relay output, which could be connected to various alarming control panel mainframes.
Chemical resistance and abrasion resistance: extrude and make jacket with high-strength, which could meet different needs;
Restorability: the linear heat sensing cable could automatically reset after alarming (under the situation of fire alarming temperature does not harm linear heat sensing cable), saving much cost for maintenance and operation;
Multiple monitoring functions: except for normal fire-alarming function, it could also monitor open circuit and short circuit faults.
Interruption resistance: four-core stranded structure has strong ability to resist electromagnetic field interruption.
Easy installation and simple maintenance
4. Application range of the products:
Cable tray; Conveyor
Power distribution device: switch cabinet, transformer, converting station, motor control center.
Filter, bag filter; Warehouse/shelf storage
Industrial process and material handling system
Bridge, wharf, shipping
Chemical storage facility
Hangar, oil
5. Technical parameter
Outer jacket configuration: PVC/High temperature resistance PVC
Standard length: 200m
Outside diameter of cable 3.5mm
Extendable 100N
Conductor material copper
Low temperature characteristics -40ºC
Ultimate temperature 190ºC
Temperature range 70ºC~140ºC
Voltage resistance The voltage resistance between core conductor and outer jacket is 10KV
Control Unit
MS2000-I Control Unit
The linear heat sensing cable MS2000-I of MS2000 linear detector interface is the controlling equipment used for monitoring temperature fluctuation of linear heat sensing cable and being connected to mainframe of intelligent fire alarm control panel. The linear heat sensing cable MS2000-I of MS2000 linear detector interface is the controlling equipment used for monitoring temperature fluctuation of linear heat sensing cable and being connected to mainframe of intelligent fire alarm control panel. Since fire alarm has locking function, MS2000-I must be disconnected to power and reset after alarming. While the fault function could automatically reset, it means that after clearing fault, fault signal of MS2000-I is automatically cleared.
Technical parameters
Plastic shell: chemical resistance, aging resistance and impact resistance;
IP rating: IP66
Linear detector interface has liquid crystal display which could show various alarming information on liquid crystal in Chinese for the convenience of user's operation.
Fire alarm simulation and fault simulation could be performed through linear detector interface.
Systematical commissioning is east and convenient.
The detector has high ability of interruption resistance adopting fine grounding measurement, isolation test and software interruption resistance technique. It is able to apply in places with high electromagnetic field interruption.
Address:
Room 546, Building Youcheng, North Tucheng West Road, Chaoyang district, Beijing
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics, Industrial Equipment & Components, Instruments & Meters, Security & Protection
Management System Certification:
ISO 9001, ISO 14001, OHSAS/ OHSMS 18001
Company Introduction:
P. T. Security Technology Co., Ltd. (simplified as P. T. S) is a leading manufacturer of Linear Heat Detection System. P. T. S aims to become a global leader in Linear Heat Detection System. P. T. S has been developing and manufacturing highly advanced linear heat detector products over 20 years.
In the year of 1994, P. T. S designed and applied the first Linear Heat Detection System for Engineering Application and laid the foundation for Linear Heat Detection system.
In the year of 2012, P. T. S was organization re-structured, and employed more experienced technical professions and scholars, who have been working in fire industry more than 10 years.
In the year of 2013, Beijing P. T. S was established for overseas market development, sales, and service.
In the year of 2014, P. T. S was certified to ISO9001: 2008.
In the year of 2015, P. T. S was approved by Factory Mutual Laboratories (FM approvals).
In the year of 2019, P. T. S was approved by Underwriters Laboratories Inc (UL approvals).